Customer Support +86-755-26975359

IsoCap I-ZF voltage sensor

The IsoCap I-ZF input connector is located at the top of the module in the figure bellow. A connector that servers to power the sensing unit, output signal and ground the sensor lay along the bottom.

Output voltage:± 10 V, ± 5 V Bandwidth (-3dB point):DC - 100 kHz Max Input delay:< 1 μs


In Stock

YES

Delivery

10 Days

Warranty

24 months

Select Options

Input Current
Accuracy
Output Voltage
- +
Add to inquiry form

Bandwidth

IsoCap I-ZF20 A50 A100 A 200 A 300 A500 A600 A1000 A2000 A
Bandwidth ( - 3 dB point)DC - 100 kHzDC - 80 kHzDC - 60 kHz
DC - 50 kHz
Power consumption @ 24 V200 mA300 mA
600 mA


Performance

Accuracy± ( 0.1 % of reading + 0.005 % range)
± ( 0.02 % of reading + 0.005 % range)
Max Input delay< 1 μs
Max total phase shift at 60 Hz< 0.01°
Isolation voltage5 kV for 1 min
Isolation voltage for transient10 kV for 50 μs
Insulation Resistance> 500 MOhm ( @ 500 V )
Thermal drift gain< ± 0.01 % / °C

Environmental

Operating temperature– 25 to 70 °C
Storage temperature– 40 to 80 °C
Mounting TypeDIN Rail and Panel
Outer Dimensions3.5” x 2.5” x 1.4”
Weight77.8 g ( 2.75 oz )

Overview

The IsoCap I-ZF is a single channel module designed for high-quality high current measurements in the range from 20 to 2000 Amperes. The IsoCap I-ZF is a combination of two units: (1) sense the current flowing through a conductor and (2) convert the signal into a standard ±10V .  The compact form factor of the IsoCap I-ZF module set allows users to setup high channel density monitoring systems, making it ideal for high performance compact systems.

Environmental

Input-Output non-linearity< 0.02 % or < 0.005 %
Max total phase shift at 50 Hz< 0.01°
Max Input delay< 1 μs
Isolation voltage5 kV for 1 min
Isolation voltage for transient± 5000 V
Insulation Resistance> 500 MOhm ( @ 500 V )

Hardware description


微信截图_20240606100911.png

    Connect external power source to power the unit. For proper functioning the power supply should provide a voltage as specified with at least 0.2 A of continuous current and 0.4 A surge during module start-up.
    Pass conductor through aperture and observe orientation for proper signal polarity.
    Securely connect one end of a 4 wire cable with corresponding connectors to IsoCap I-ZF main unit, and the other end to the inputs of the sensing unit.